Coalescence separators with bypass
Usage and operation
Coalescence separators with bypass NIXOR-NKB, NIXOR-NKOB are used to pre-treat rainwater sewage from urban water catchment areas such as parking lots, roads, maneuvering areas, etc. We are able to achieve high efficiency of sewage treatment from petroleum substances thanks to the use of coalescence material which aid the gravitational separation of oil pollution. Sewage flowing into the device go through an outlet located in the main pipe and are distributed throughout the entire tank. This is where gravitational separation of pollutants found in sewage occurs. Then they flow through the coalescence material, where smaller elements of oil pollution that do not float under the influence of gravity are captured. The treated sewage flows through the siphon outlet to the main pipe. The devices are equipped in float closures that protect against the penetration of oil contaminants into the drain. At the inflow of sewage in quantity greater than the nominal size, excess wastewater flows directly to the outflow. In the case of separators without a NIXOR-NKB settling tank, incoming sewage must be pre-treated in a settling tank with adequate capacity.
Construction
Coalescence separator frames with bypass NIXOR-NKB and NIXOR-NKOB are made as concrete, reinforced concrete or plastic tanks. Equipment made of PE, PU and stainless steel is assembled in the production plant. The assembly of the largest devices whose frames are delivered in elements (designation B in the type of device), takes place on the construction site. Coalescence separators with bypass can be equipped with oil and sludge level sensors.
|
|
|
NIXOR-NKB Coalescence separator with bypass
|
NIXOR-NKOB Coalescence separator with bypass
|
|
NIXOR-NKB coalescence separator with bypass
Device type |
Nominal size |
Capacity |
External diameter of tank |
Height of inflow |
Minimum depth* |
Pipeline diameter |
Oil collection capacity |
Data sheet |
Declaration of Conformity |
NS |
Qmax |
DW |
HW |
Z |
DN |
VOL |
dm3/s |
m |
mm |
m |
mm |
dm3 |
NKB 3/30 |
3 |
30 |
1200 |
0,58 |
0,77 |
≤400 |
270 |
|
|
NKB 6/60 |
6 |
60 |
1200 |
0,58 |
0,77 |
≤400 |
270 |
|
|
NKB 10/100 |
10 |
100 |
1200 |
0,58 |
0,77 |
≤400 |
270 |
|
|
NKB 15/150 |
15 |
150 |
1500 |
0,80 |
0,85 |
≤400 |
790 |
|
|
NKB 20/200 |
20 |
200 |
1500 |
0,80 |
0,85 |
≤500 |
790 |
|
|
NKB 30/300 |
30 |
300 |
2000 |
1,00 |
0,85 |
≤500 |
1830 |
|
|
NKB 40/400 |
40 |
400 |
2000 |
1,00 |
0,85 |
≤500 |
1830 |
|
|
NKB 50/500 |
50 |
500 |
2000 |
1,55 |
0,80 |
≤500 |
2030 |
|
|
NKB 60/600 |
60 |
600 |
2000 |
1,55 |
1,10 |
≤630 |
2030 |
|
|
NKB 65/650 |
65 |
650 |
2000 |
1,55 |
1,10 |
≤630 |
2030 |
|
|
NKB 70/700 |
70 |
700 |
2000 |
1,55 |
1,10 |
≤630 |
2030 |
|
|
NKB 75/750 |
75 |
750 |
2000 |
1,55 |
1,10 |
≤630 |
2030 |
|
|
NKB 80/800 |
80 |
800 |
2000 |
1,55 |
1,10 |
≤630 |
2030 |
|
|
NKB 90/900 B |
90 |
900 |
2000 |
1,55 |
1,30 |
≤800 |
2030 |
|
|
NKB 100/1000 B |
100 |
1000 |
2000 |
1,55 |
1,30 |
≤800 |
2030 |
|
|
NKB 110/1100 B |
110 |
1100 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 120/1200 B |
120 |
1200 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 125/1250 B |
125 |
1250 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 130/1300 B |
130 |
1300 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 140/1400 B |
140 |
1400 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 150/1500 B |
150 |
1500 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 160/1600 B |
160 |
1600 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 170/1700 B |
170 |
1700 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 180/1800 B |
180 |
1800 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 190/1900 B |
190 |
1900 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
NKB 200/2000 B |
200 |
2000 |
2500 |
1,80 |
1,55 |
≤1000 |
4100 |
|
|
* Z - designated for the maximum pipe diameter for a given device; individual solutions will be used in the case of depth less than the minimum
B - devices delivered in elements for assembly on the construction site by the ordering party.
NIXOR reserves the right to make design changes without prior notification.
It is possible to increase the capacity of the sludge and oil storage for individual situations.
NIXOR-NKOB bypass coalescence separator with settling tank
Device type |
Nominal size |
Capacity |
Średnica wew. zbiornika |
Height of inflow |
Minimum depth* |
Pipeline diameter |
Oil collection capacity |
Pojemność części osadowa |
Data sheet |
Declaration of Conformity |
NS |
Qmax |
DW |
HW |
Z |
DN |
VOL |
VOL |
dm3/s |
m |
mm |
m |
mm |
dm3 |
dm3 |
NKOB 3/30/300 |
3 |
30 |
1200 |
0,69 |
0,66 |
≤315 |
270 |
300 |
|
|
NKOB 3/30/600 |
3 |
30 |
1500 |
0,76 |
0,89 |
≤315 |
430 |
600 |
|
|
NKOB 6/60/600 |
6 |
60 |
1500 |
0,76 |
0,89 |
≤315 |
430 |
600 |
|
|
NKOB 6/60/1200 |
6 |
60 |
1500 |
1,10 |
0,80 |
≤315 |
430 |
1200 |
|
|
NKOB 10/100/1000 |
10 |
100 |
1500 |
0,99 |
0,91 |
≤400 |
430 |
1000 |
|
|
NKOB 10/100/2000 |
10 |
100 |
1500 |
1,56 |
0,84 |
≤400 |
430 |
2000 |
|
|
NKOB 10/100/3000 |
10 |
100 |
2000 |
1,38 |
0,67 |
≤400 |
770 |
3000 |
|
|
NKOB 15/150/1500 |
15 |
150 |
1500 |
1,45 |
0,95 |
≤400 |
790 |
1500 |
|
|
NKOB 15/150/3000 |
15 |
150 |
2000 |
1,56 |
0,69 |
≤400 |
1420 |
3000 |
|
|
NKOB 20/200/2000 |
20 |
200 |
1500 |
1,74 |
0,91 |
≤500 |
790 |
2000 |
|
|
NKOB 20/200/4000 |
20 |
200 |
2000 |
1,88 |
0,77 |
≤500 |
1420 |
4000 |
|
|
NKOB 30/300/3000 |
30 |
300 |
2000 |
1,64 |
0,81 |
≤500 |
1710 |
3000 |
|
|
NKOB 30/300/6000 B |
30 |
300 |
2500 |
1,91 |
0,84 |
≤500 |
2690 |
6000 |
|
|
NKOB 40/400/4000 B |
40 |
400 |
2000 |
1,96 |
0,79 |
≤500 |
1710 |
4000 |
|
|
NKOB 40/400/8000 B |
40 |
400 |
2500 |
2,32 |
0,83 |
≤500 |
2690 |
8000 |
|
|
NKOB 50/500/5000 (2000) B |
50 |
500 |
2000 |
2,83 |
0,82 |
≤500 |
2030 |
5000 |
|
|
NKOB 50/500/5000 (2500) B |
50 |
500 |
2500 |
2,26 |
0,79 |
≤500 |
3210 |
5000 |
|
|
NKOB 50/500/10000 B |
50 |
500 |
3000 |
2,65 |
0,80 |
≤500 |
4640 |
10000 |
|
|
NKOB 60/600/6000 (2000) B |
60 |
600 |
2000 |
3,15 |
1,00 |
≤630 |
2030 |
6000 |
|
|
NKOB 60/600/6000 (2500) B |
60 |
600 |
2500 |
2,46 |
0,99 |
≤630 |
3210 |
6000 |
|
|
NKOB 60/600/12000 B |
60 |
600 |
3000 |
2,09 |
0,96 |
≤630 |
4640 |
6000 |
|
|
NKOB 65/650/6500 (2000) B |
65 |
650 |
2000 |
3,31 |
0,94 |
≤630 |
2030 |
6500 |
|
|
NKOB 65/650/6500 (2500) B |
65 |
650 |
2500 |
2,56 |
0,99 |
≤630 |
3210 |
6500 |
|
|
NKOB 70/700/7000 (2000) B |
70 |
700 |
2000 |
3,47 |
0,98 |
≤630 |
2030 |
7000 |
|
|
NKOB 70/700/7000 (2500) B |
70 |
700 |
2500 |
2,67 |
0,98 |
≤630 |
3210 |
7000 |
|
|
NKOB 75/750/7500 (2000) B |
75 |
750 |
2000 |
3,63 |
1,02 |
≤630 |
2030 |
7500 |
|
|
NKOB 75/750/7500 (2500) B |
75 |
750 |
2500 |
2,77 |
0,98 |
≤630 |
3210 |
7500 |
|
|
NKOB 80/800/8000 (2000) B |
80 |
800 |
2000 |
3,79 |
0,96 |
≤630 |
2030 |
8000 |
|
|
NKOB 80/800/8000 (2500) B |
80 |
800 |
2500 |
2,87 |
0,98 |
≤630 |
3210 |
8000 |
|
|
NKOB 90/900/9000 (2500) B |
90 |
900 |
2500 |
3,07 |
1,18 |
≤800 |
3210 |
9000 |
|
|
NKOB 90/900/9000 (3000)B |
90 |
900 |
3000 |
2,51 |
1,14 |
≤800 |
4640 |
9000 |
|
|
NKOB 100/1000/10000 (2500) B |
100 |
1000 |
2500 |
3,28 |
1,17 |
≤800 |
3210 |
10000 |
|
|
NKOB 100/1000/10000 (3000) B |
100 |
1000 |
3000 |
2,65 |
1,20 |
≤800 |
4640 |
10000 |
|
|
NKOB 110/1100/11000 B |
110 |
1100 |
3000 |
2,96 |
1,39 |
≤1000 |
5960 |
11000 |
|
|
NKOB 120/1200/12000 B |
120 |
1200 |
3000 |
3,10 |
1,35 |
≤1000 |
5960 |
12000 |
|
|
NKOB 125/1250/12500 B |
125 |
1250 |
3000 |
3,17 |
1,38 |
≤1000 |
5960 |
12500 |
|
|
NKOB 130/1300/13000 B |
130 |
1300 |
3000 |
3,24 |
1,41 |
≤1000 |
5960 |
13000 |
|
|
NKOB 140/1400/14000 B |
140 |
1400 |
3000 |
3,39 |
1,36 |
≤1000 |
5960 |
14000 |
|
|
NKOB 150/1500/15000 B |
150 |
1500 |
3000 |
3,53 |
1,42 |
≤1000 |
5960 |
15000 |
|
|
NKOB 160/1600/16000 B |
160 |
1600 |
3000 |
3,67 |
1,38 |
≤1000 |
5960 |
16000 |
|
|
NKOB 170/1700/17000 B |
170 |
1700 |
3000 |
3,81 |
1,34 |
≤1000 |
5960 |
17000 |
|
|
NKOB 180/1800/18000 B |
180 |
1800 |
3000 |
3,95 |
1,40 |
≤1000 |
5960 |
18000 |
|
|
NKOB 190/1900/19000 B |
190 |
1900 |
3000 |
4,09 |
1,36 |
≤1000 |
5960 |
19000 |
|
|
NKOB 200/2000/20000 B |
200 |
2000 |
3000 |
4,23 |
1,42 |
≤1000 |
5960 |
20000 |
|
|
* Z - designated for the maximum pipe diameter for a given device; individual solutions will be used for with less than minimum depth.
B - devices delivered in elements for assembly on the construction site by the ordering party.
NIXOR reserves the right to make design changes without prior notification.
It is possible to increase the capacity of the sludge and oil storage for individual situations.
Aby zobaczyć pełną specyfikację produktu proszę otworzyć stronę na komputerze.